1.Two-input phase comparator in a static relay is made up of a 

  • ATransformer amplifier.
  • BTransistor logic circuit.
  • CRectifier bridge.
  • DThyristor bridge.
Answer / Hint Save Question Comment On Question
Correct Answer : (C)

Rectifier bridge.

Explanation:

Two-input phase comparator in a static relay is made up of a Rectifier bridge.

2.The phase comparators in case of static relay and electromechanical relay normally are 

  • ACosine and sine comparators respectively.
  • BSine and cosine comparators respectively.
  • CBoth are sine comparators.
  • DBoth are cosine comparators.
Answer / Hint Save Question Comment On Question
Correct Answer : (A)

Cosine and sine comparators respectively.

Explanation:

The phase comparators in case of static relay and electromechanical relay normally are Cosine and sine comparators respectively.

3.Merz-Price protection is employed for protection of

  • AAlternators
  • BTransformers
  • CTransmission lines.
  • DBoth (a) and (b) 
Answer / Hint Save Question Comment On Question
Correct Answer : (D)

Both (a) and (b) 

Explanation:

Merz-Price protection is employed for protection of Alternators and Transformers.

4.A negative-sequence voltage in the stator induces

  • AHigh frequency currents in the rotor.
  • BHigh frequency voltage in the rotor.
  • CLow frequency currents in the rotor.
  • DHigh frequency currents in the stator.
Answer / Hint Save Question Comment On Question
Correct Answer : (A)

High frequency currents in the rotor.

Explanation:

5.The short-circuit current of an alternator, in case of line to line fault, depends on its 

  • AShort-circuit resistance. 
  • BTransient reactance. 
  • CSynchronous reactance.
  • DNone of the above.
Answer / Hint Save Question Comment On Question
Correct Answer : (C)

Synchronous reactance.

Explanation:

The short-circuit current of an alternator, in case of line to line fault, depends on its Synchronous reactance.

6.We do not require any protection against prime mover failure in case of 

  • ATurbo-generator sets.
  • BHydro-generator sets. 
  • CDiesel-engine driven alternators.
  • DBack pressure turbo-generators.
Answer / Hint Save Question Comment On Question
Correct Answer : (A)

Turbo-generator sets.

Explanation:

We do not require any protection against prime mover failure in case of Turbo-generator sets.

7.For the protection of stator winding of an alternator against internal fault involving ground, the relay used is a 

  • ABiased differential relay.
  • BDirectional overcurrent relay. 
  • CPlain impedance relay.
  • DBuchholz relay. 
Answer / Hint Save Question Comment On Question
Correct Answer : (A)

Biased differential relay.

Explanation:

8.The bias factor S in unit protection synchronous generator

  • ALies between 0.05 and 0.1 pu.
  • BIs less than 0.05 pu
  • CLies between 0.1 to 0.25 pu.
  • DIs greater than 0.025 pu.
Answer / Hint Save Question Comment On Question
Correct Answer : (A)

Lies between 0.05 and 0.1 pu.

Explanation:

9.Field failure in an alternator occurs due to

  • AFailure of exciter
  • BFaulty field circuit breaker.
  • CInrush of large currents
  • DBoth (a) and (b) 
Answer / Hint Save Question Comment On Question
Correct Answer : (D)

Both (a) and (b) 

Explanation:

Field failure in an alternator occurs due to Failure of exciter and Faulty field circuit breaker.

10.A soon as a fault develops in a generator stator, it is essential to suppress field excitation, otherwise

  • ATerminal voltage will drop.
  • BIt may lead to loss of synchronism.
  • CIt will continue to supply power to the stator winding fault. 
  • DAll of the above. 
Answer / Hint Save Question
Correct Answer : (C)

It will continue to supply power to the stator winding fault. 

Explanation:

11.If there is an open circuit in the field circuit of a generator 

  • AThe generator will continue to operate as an induction generator supplying load at a very low leading power factor.
  • BThe supply voltage will drop, and the system stability will be affected.
  • CThe circulating current at slip frequency may overhead the generator.
  • DAll of the above. 
Answer / Hint Save Question Comment On Question
Correct Answer : (D)

All of the above. 

Explanation:

12.The earth fault in stator causes 

  • AArcing to core.
  • BSevere heating in conductors and thereby damaging the insulation.
  • COpen-circuit in the stator 
  • DBoth (a) and (b) 
Answer / Hint Save Question Comment On Question
Correct Answer : (D)

Both (a) and (b) 

Explanation:

The earth fault in stator causes Arcing to core and Severe heating in conductors and thereby damaging the insulation.

13.Failure of insulation on stator winding of generator results in 

  • AShort circuit between turns.
  • BShort circuit between one or more phases and earth.
  • CShort circuit between phases.
  • DAll of the above. 
Answer / Hint Save Question Comment On Question
Correct Answer : (D)

All of the above. 

Explanation:

14.The magnitude of earth-fault current for a given fault position within a winding depends upon 

  • AThe winding connections.
  • BThe method of neutral grounding. 
  • CUnmatched characteristics of CTs.
  • DBoth (a) and (b)
Answer / Hint Save Question Comment On Question
Correct Answer : (D)

Both (a) and (b)

Explanation:

15.For the protection of a large squirrel-cage induction motor against single phase normally 

  • AAn overcurrent relay is used.
  • BA differential relay is used.
  • CA directional relay is used.
  • DNegative sequence current sensitive relay is used.
Answer / Hint Save Question Comment On Question
Correct Answer : (D)

Negative sequence current sensitive relay is used.

Explanation:

16.The main function of undervoltage protective device generally employed with a motor starter is to 

  • AOpen the supply circuit on failure of power supply.
  • BControl the motor voltage. 
  • CPrevent the opening of supply circuit.
  • DNone of the above. 
Answer / Hint Save Question Comment On Question
Correct Answer : (A)

Open the supply circuit on failure of power supply.

Explanation:

17.While adding extra stop buttons to an existing control system they must be in 

  • AParallel to the load.
  • BSeries with the contactor coil.
  • CSeries with the motor. 
  • DParallel to the start button. 
Answer / Hint Save Question Comment On Question
Correct Answer : (B)

Series with the contactor coil.

Explanation:

18.Negative-sequence currents flow in the stator windings of an ac motor due to 

  • AUnbalanced in the supply voltage 
  • BUnbalanced load
  • CPhase reversal
  • DWither (a) or (b) 
Answer / Hint Save Question Comment On Question
Correct Answer : (D)

Wither (a) or (b) 

Explanation:

19.A negative sequence relay is commonly used to protect

  • AAn alternator
  • BA transformer 
  • CA transmission line
  • DA bus bar
Answer / Hint Save Question Comment On Question
Correct Answer : (A)

An alternator

Explanation:

A negative sequence relay is commonly used to protect an alternator.

20.Earth fault protection for an electric motor is provided by

  • AInstantaneous overcurrent relay.
  • BInstantaneous relay having a setting of approximately 30% of motor rated current in the residual circuits of two CTs.
  • CGround wire
  • DBoth (b) and (c) 
Answer / Hint Save Question Comment On Question
Correct Answer : (D)

Both (b) and (c) 

Explanation:

Earth fault protection for an electric motor is provided by Instantaneous relay having a setting of approximately 30% of motor rated current in the residual circuits of two CTs and Ground wire.