Q.

When a line-to-ground fault occurs, the current in the faulted phase is  100 A. the zero-sequence current in this case will be  :

  • AZero
  • B33.3 A
  • C66.6 A
  • D100 A
Correct Answer : (B)

33.3 A

Hints :